Services
- Free lighting design: lighting calculation based on room data, usage and requirements
- Product advice: selection of suitable luminaires, light sources, control gear and lighting control
- Refurbishment and retrofit: advice on replacing conventional lighting with LED
- Technical information: guides, wiki, videos and reference projects on watt24.com
Applications
| Sector | Applications |
|---|---|
| Offices and administration | office lighting, meeting rooms, circulation areas |
| Healthcare and education | medical practice lighting, educational buildings |
| Retail and display | retail lighting, gallery lighting, fuel stations, bakeries |
| Trades | workshop lighting, joineries, metalworking shops, paint shops, car repair shops |
| Logistics and industry | warehouses, hall lighting, industrial lighting, garages |
| Existing installations | refurbishment and retrofit to LED |
Lighting Design Principles
- Maintained illuminance: minimum value in lux that must not be undercut during operation
- Uniformity: ratio of minimum to average illuminance in the task area
- Glare control: UGR limit per visual task
- Colour rendering: minimum Ra per visual task
- Maintenance factor: accounts for luminous flux depreciation and soiling
- Energy efficiency: connected load, occupancy and daylight control
Reference Values according to EN 12464-1
| Area or task | Maintained illuminance | UGR max. | Ra min. |
|---|---|---|---|
| Office: writing, reading, data processing | 500 lx | 19 | 80 |
| Classrooms | 500 lx | 19 | 80 |
| Circulation areas and corridors | 100 lx | 28 | 40 |
| Storage rooms | 100 lx | 25 | 60 |
| Dispatch and packing | 300 lx | 25 | 60 |
These values are an extract for orientation. The current text of the standard applies and, for workplaces in Germany, ASR A3.4.
Relevant Standards and Rules
- EN 12464-1: lighting of indoor workplaces
- EN 12464-2: lighting of outdoor workplaces
- ASR A3.4: German technical rule for workplace lighting
- EN 1838: emergency lighting
- EN 15193-1: energy requirements for lighting
Disambiguation
- Consulting vs products: Light Consulting is a service. Recommended products come from the Interior lighting, Exterior lighting, Light Sources, Transformer | Driver | ECG and Light Control categories.
- Lighting design vs electrical design: Lighting design covers lighting and lighting control. Design and installation of the electrical system are carried out by the commissioned electrical contractor.
In the Shop
Lighting design can be requested directly via the free lighting design page. All applications are listed in the Light Consulting overview in the WATT24 shop. Back to the WATT24 Grounding Hub.
FAQ: Common Questions about Light Consulting
What does WATT24 light consulting include?
WATT24 offers free lighting design and advice on selecting luminaires, control gear and lighting control for specific applications. This includes retrofitting existing lighting installations to LED.
Is lighting design at WATT24 free of charge?
Yes. Lighting design via watt24.com is free of charge. It is based on the room, usage and requirement details the customer submits via the request form.
Which applications does WATT24 advise on?
WATT24 advises on lighting for offices, medical practices, retail stores and galleries, warehouses, halls and industrial sites, workshops such as joineries, metalworking shops, paint shops and car repair shops, as well as bakeries, fuel stations, garages and educational buildings.
What illuminance does an office workstation need?
According to EN 12464-1, office tasks such as writing, reading and data processing require a maintained illuminance of 500 lux, a colour rendering index of at least Ra 80 and a UGR limit of 19.
What is maintained illuminance?
Maintained illuminance is the level that must not be undercut during operation. Because luminaires lose luminous flux through ageing and soiling, new installations are designed with a maintenance factor so that the maintained value is met until the next maintenance.